• Kohler Co.
provides one-source responsibility for the generating system and
accessories.
• Skid mount OR Acoustic
enclosed
• The generator set and its components are protype-tested,
factory-built, and production-tested.
• Unit-mounted radiator with 50ºC (122ºF) ambient air capability.
• Skid and vibration isolators.
• Subbase fuel tank, 470 L (124 gal.).
• Dry type air filter.
• Main line circuit breaker.
• Microprocessor controller.
• Battery, battery rack, and cables.
• Industrial 9 dB(A) reduction exhaust silencer (loose).
• 24-volt battery charging alternator.
• Single-bearing alternator with insulation class H.
• NEMA-MG21, UTE NF C51.1111, VDE 0530, BS 4999 CSA standards
conpliance for temperature rise and motor starting.
• Sustained short-circuit current greater than 300% of the rated
current for up to 10 seconds.
• Vacuum-impregnated windings with fungus-resistant epoxy varnish
for dependability and long life.
• Self-ventilated and dripproff construction.
• Superior voltage waveform from a two-thirds pitch stator and
skewed rotor.
Prime Ratings:
|
300 kW
(375 kVa)
|
Standby Ratings:
|
330 kW
(413 kVa)
|
Hertz:
|
50 Hz
|
Alternator Type:
|
4-pole,
Rotating-Field
|
Engine Manufacturer:
|
Volvo
|
Engine Model:
|
TAD1241GE
|
Cylinder Arrangement:
|
6
Inline
|
Max Power at Rated RPM:
|
354 kWm
(474 BHP)
|
Prime Fuel Consumption at
|
|
100% load:
|
74.4
Lph (19.7 gph)
|
75% load:
|
55.0
Lph (14.5 gph)
|
50% load:
|
37.4
Lph (9.9 gph)
|